Heating circuits
Setting up the heating circuits
All Komplett III can control up to three individual heating circuits with a great variety of programs
as well as day/time set back. To set up the heating circuits it is important to have the project docu-
mentation available in order to set the system up as it has been sold originally.
The layout and controls can be done in more than fifty ways and we will in this document try to
explain the basic functions. Please use the users manual as reference if deeper information is
needed.
For the circuits to work you need the following components installed:
Components for heating circuits
Shunt valve 3 way
Shunt motor 120s ESBE
Flow sensor, article 301701
Outdoor sensor, article 301702
Room sensor, article 30171
Activating the heating system menu
Heating system menus
The flow sensors enables and activates the menus for
each heating circuit. The first flow sensor needs to be
connected to G7 on the main board in order to activate
heating circuit one. The second and third heating circuit
is controlled from the expansion board and are at port G9
and G10.
NOTE: If the flow sensor for the desired heating circuit
isn´t connected the menu for the circuit will not appear in
the controller!
A electrical diagram is available in the full manual for the
Komplett III boilers.
Heating program options
Room
If the program ROOM is choosen the shunt motor will regulate the shunt valve to maintain a certain
room temperature getting it´s reference from the room sensor. One room sensor is used for each
heating circuit using this program. The active sensors in this set up is the flow sensor and room
sensor.
It is possible to use the ENERGY SAVER function to set back the room temperature with the de-
sired amount of degrees on two different times each individual weekday.
Recommended to use when: The building uses radiators and the room sensor is placed in a loca-
tion where it isn´t affected by direct sunlight or chill from doors opening and closing. It should be
placed in a central location of the building and not on a outer wall.
Not recommended to use when: The building uses radiant floor heating / under floor heating.
Effecta AB - Västra Rågdalsvägen 21 - 434 99 Kungsbacka - 0300 - 22320 - info@effecta.se
Amount used per heating circuit
1 pcs. per heating circuit
1 pcs. per heating circuit
1 pcs. per heating circuit
1 pcs. common for all available heating circuits.
1 pcs. per heating circuit
Shunt control 1
Program
Flow temp.
Radiator pump
Constant flow
Enegy saver
Backend prot.
Constant flow
22 (20)°C
On
60°C
>
Yes
19