Minimum Time Between Two Successive OCS Orders: sets a minimum
time space (from 0 to 3600 seconds or from 0 to 1440 minutes) between
consecutive updates of the valve position, either by operating on the valve
(local control) or by sending the valve control objects (remote control). This
prevents continuous operation of the valve in case the OCS changes
frequently.
The above two parameters are available for each valve (in case of having two valves).
MODE SWITCH DELAYS
These delays apply to the mode switchovers (heating to cooling, and vice versa), and
consist in waiting a certain time before opening the valve of the target mode after
closing the valve of the source mode.
Heating to Cooling Switch Delay: from 0 to 3600 seconds and from 0 to
1440 minutes.
Cooling to Heating Switch Delay: from 0 to 3600 seconds and from 0 to
1440 minutes.
ADVANCED VALVE CONFIGURATION
Minimum Valve Opening: enables or disables a new tab to configure the
minimum valve opening level. See section 2.5.2.1.