LED backlight to confirm the press of the buttons as well as showing states. Tecla 55 is a fully customisable solution for the control of rooms where user control of air conditioning systems, lighting, blinds, scenes, etc. is required.
Page 5
Tecla 55 Analogue/digital input configurable as temperature probe. Thermostat function. Heartbeat or periodical “still-alive” notification. https://www.zennio.com Technical Support: https://support.zennio.com...
Proximity and Luminosity Sensors. Figure 1. Schematic diagram of Tecla 55. Tecla 55 is connected to the KNX bus through the built-in terminal (3). An external DC power supply is not needed. A short press on the programming button (5) will make the device enter the programming mode.
Tecla 55 1.3 START-UP AND POWER LOSS After download or device reset it is necessary to wait for about 2 minutes without performing any action in order to make it possible a proper calibration of: Proximity sensor. Luminosity sensor. Button presses.
Tecla 55 2 CONFIGURATION After importing the corresponding database in ETS and adding the device into the topology of the project, the configuration process begins by entering the Parameters tab of the device. 2.1 GENERAL In order to allow the device to perform the desired functions, a number of options must be parameterized, either related to its general behaviour or to advanced features.
Page 9
Tecla 55 The following parameters are shown: Device Orientation [Horizontal (Rotated) / Vertical (Rotated)] : enables horizontal or vertical orientation to be assigned to the device, for easy identification of the push-buttons during configuration process (ETS will show a figure with the final distribution of the push-buttons). To prevent inconsistency...
Page 10
Tecla 55 Note: the first sending after download or bus failure takes place with a delay of up to 255 seconds, to prevent bus overload. The following sendings march the period set. Device Recovery Objects (Send 0 and 1) [disabled/enabled]: this parameter lets the integrator activate two new communication objects (“[Heartbeat]...
For detailed information about the functionality and the configuration of the related parameters, please refer to the specific manual "Capacitive Touch Switches" available in the Tecla 55 product section at the Zennio homepage, www.zennio.com. 2.1.4 AMBIENT LUMINOSITY SENSOR Capacitive touch switches incorporate a luminosity sensor to receive and monitor ambient brightness measurement.
For detailed information about the functionality and the configuration of the related parameters, please refer to the specific manual "Capacitive Touch Switches" available in the Tecla 55 product section at the Zennio homepage, www.zennio.com. 2.3 INPUTS Capacitive touch switches can incorporate analogue/digital inputs configurable as a Temperature Probe, to connect a temperature from Zennio.
KNX standard or the application program itself. Note: The objects shown in this table are from model Tecla 55 X6. Please note that certain objects will not be available in models with less push buttons.
Page 14
Tecla 55 1 Byte C R - - - DPT_Scaling 0% - 100% [General] Luminosity (Percentage) 0% ... 100% 1 Bit C - W - - DPT_DayNight [General] Backlight Mode 0 = Night Mode; 1 = Normal Mode 1 Bit...
Page 15
Tecla 55 (Start Pressing) Switch Between 1 Bit C - - T - DPT_UpDown [Btn][Ix] Shutter - Move Up and Down [Btn][Ix] Two Objects - Long Send Selected Value on Long 1 Bit C - W T - DPT_Switch Press...
Page 16
Tecla 55 (Short Press) Left = Stop/Step 1 Bit C - - T - DPT_Step [Btn][Px] Shutter - Stop/Step Up; Right = Stop/Step Down (End Pressing) Left = Stop-Up; 1 Bit C - - T - DPT_Trigger [Btn][Px] Shutter - Stop...
Page 17
Tecla 55 0x0 (Stop) 0x1 (Dec. by 100%) 0x7 (Dec. by 1%) (Long Press) Lower = Brighter; 4 Bit C - W T - DPT_Control_Dimming [Btn][Px] Light - Dimming 0x8 (Stop) Upper = Darker 0xD (Inc. by 100%) 0xF (Inc. by 1%)
Page 18
Tecla 55 1 Bit C - W - - DPT_Ack [Tx] Special Mode: Comfort 0 = Nothing; 1 = Trigger 1 Bit C - W - - DPT_Switch [Tx] Special Mode: Comfort 0 = Off; 1 = On 1 Bit...
Page 19
Tecla 55 1 Bit C R - T - DPT_Switch [Tx] [Sx] Control Variable 2-Point Control 1 Bit C R - T - DPT_Switch [Tx] [Sx] Control Variable PI Control (PWM) 0 = PI Signal 0%; 1 = PI Signal...
Page 20
Join and send us your inquiries about Zennio devices: https://support.zennio.com Zennio Avance y Tecnología S.L. C/ Río Jarama, 132. Nave P-8.11 45007 Toledo (Spain). Tel. +34 925 232 002. www.zennio.com info@zennio.com...