Zennio MAXinBOX FC 0-10V FAN Technical Documentation

2 or 4-pipe fan-coil controller with 0-10 vdc fan control signal
Hide thumbs Also See for MAXinBOX FC 0-10V FAN:

Advertisement

Quick Links

2 or 4-pipe FAN-COIL controller with 0-10 VDC fan control signal
ZCL-FC010F
FEATURES
2 x 0-10 VDC individual outputs for fan control
4 individual outputs (suitable for capacitive loads, maximum 140 µF)
4 analog/digital inputs
Manual output operation of 0-10 VDC and individual outputs with push
button and LED status indicator
10 logic functions
Output timing facilities
Total data saving on power failure
Integrated KNX BCU (TP1-256)
Dimensions 67 x 90 x 79 mm (4.5 DIN units)
DIN rail mounting according to IEC 60715 TH35, with fixing clamp
Possibility of connecting different phases in adjacent outputs
Conformity with the CE, UKCA, RCM directives (marks on the right
side)
1. Analog/Digital inputs
5. Programming/Test button
Programming/Test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe
mode. If this button is held for more than 3 seconds, the device enters the test mode.
Programming/Test LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The manual mode
is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it starts a blue blinking sequence.
GENERAL SPECIFICATIONS
CONCEPT
Type of device
Voltage (typical)
Voltage range
KNX supply
Maximum
consumption
Connection type
External power supply
Operation temperature
Storage temperature
Operation humidity
Storage humidity
Complementary characteristics
Protection class / Overvoltage category
Operation type
Device action type
Electrical stress period
Degree of protection / Pollution degree
Installation
Minimum clearances
Response on KNX bus failure
Response on KNX bus restart
Operation indicator
Weight
PCB CTI index
Housing material / Ball pressure test temperature
¹ Maximum consumption in the worst-case scenario (KNX Fan-In model).
© Zennio Avance y Tecnología S.L.
2. 0-10 VDC outputs
6. Programming/Test LED
Voltage
29 VDC (typical)
24 VDC¹
Edition 15
MAXinBOX FC 0-10V FAN
2
3
4
5
6
7
3. Output status LED
7. Individual outputs
DESCRIPTION
Electric operation control device
29 VDC SELV
21-31 VDC
mA
11
15
Typical TP1 bus connector for 0.8 mm Ø rigid cable
Not required
0 .. +55 °C
-20 .. +55 °C
5 .. 95%
5 .. 95%
Class B
II / III (4000 V)
Continuous operation
Type 1
Long
IP20 / 2 (clean environment)
Independent device to be mounted inside electrical panels with DIN rail (IEC
60715)
Not required
Data saving according to parameterization
Data recovery according to parameterization
The programming LED indicates programming mode (red) and test mode
(green). Each output LED indicates its status
248 g
175 V
PC FR V0 halogen free / 75 °C (housing) - 125 °C (connectors)
Further information
TECHNICAL DOCUMENTATION
Figure 1: MAXinBOX FC 0-10V FAN
4. Output control button
8. KNX connector
9. Fixing clamp
mW
319
360
www.zennio.com
1
8
9
Page 1/2

Advertisement

loading

Summary of Contents for Zennio MAXinBOX FC 0-10V FAN

  • Page 1 DIN rail mounting according to IEC 60715 TH35, with fixing clamp • Possibility of connecting different phases in adjacent outputs • Conformity with the CE, UKCA, RCM directives (marks on the right Figure 1: MAXinBOX FC 0-10V FAN side) 1. Analog/Digital inputs 2. 0-10 VDC outputs 3. Output status LED 4.
  • Page 2 Connection method Screw terminal block (0.5 Nm max.) Cable cross-section 0.5-2.5 mm² (IEC) / 26-12 AWG (UL) Output per common Attaching MAXinBOX FC 0-10V FAN to DIN rail: INPUTS SPECIFICATIONS AND CONNECTIONS CONCEPT DESCRIPTION Number of inputs Inputs per common Operation voltage +3.3 VDC in the common...

This manual is also suitable for:

Zcl-fc010f