Zennio MAXinBOX FC 0-10V VALVE User Manual

Zennio MAXinBOX FC 0-10V VALVE User Manual

Two/four-pipe fan coil controller with 0-10 vdc valve control signal
Hide thumbs Also See for MAXinBOX FC 0-10V VALVE:

Advertisement

Quick Links

MAXinBOX FC 0-10V VALVE
Two/Four-Pipe Fan Coil Controller
with 0-10 VDC Valve Control Signal
ZCL-FC010V
Application Program Version: [1.0]
User Manual Version: [1.0]_a
www.zennio.com

Advertisement

Table of Contents
loading

Summary of Contents for Zennio MAXinBOX FC 0-10V VALVE

  • Page 1 MAXinBOX FC 0-10V VALVE Two/Four-Pipe Fan Coil Controller with 0-10 VDC Valve Control Signal ZCL-FC010V Application Program Version: [1.0] User Manual Version: [1.0]_a www.zennio.com...
  • Page 2: Table Of Contents

    MAXinBOX FC 0-10V VALVE CONTENTS Contents ............................2 1 Introduction ..........................3 1.1 MAXinBOX FC 0-10V VALVE ....................3 1.2 Installation ........................4 1.3 Start-up and Power Loss ....................5 2 Configuration ........................... 6 2.1 General ..........................6 2.2 Inputs ..........................8 2.3 Individual Binary Outputs ....................
  • Page 3: Introduction

    (each with its own valve) and a fan system with up to four speeds. At a glance, the most outstanding features of MAXinBOX FC 0-10V VALVE are: 1 control module for two-pipe or four-pipe fan coil units with either valves controlled through a 0-10V DC signal proportional to the opening level, or valves with their own KNX actuator (remote valve control).
  • Page 4: Installation

    Manual operation / supervision of the relay outputs and the 0-10 VDC signals through the on-board pushbuttons and LEDs. 1.2 INSTALLATION MAXinBOX FC 0-10V VALVE connects to the KNX bus through the on-board KNX connector. Once the device is provided with power from the KNX bus, both the individual address and the associated application program may be downloaded.
  • Page 5: Start-Up And Power Loss

    1.3 START-UP AND POWER LOSS During the start-up of the device, the Prog./Test LED will blink in blue colour for a few seconds before MAXinBOX FC 0-10V VALVE is ready. External orders will not be executed during this time, but afterwards.
  • Page 6: Configuration

    MAXinBOX FC 0-10V VALVE 2 CONFIGURATION 2.1 GENERAL ETS PARAMETERISATION Figure 2 General screen. After importing the corresponding database in ETS and adding the device into the topology of the desired project, the configuration process begins by right-clicking into the device and selecting Edit parameters.
  • Page 7 MAXinBOX FC 0-10V VALVE 0” and “Reset 1”), which will be sent to the KNX bus with values “0” and “1” respectively whenever the device begins operation (for example, after a bus power failure). It is possible to parameterise a certain delay for this sending (0 to 255 seconds).
  • Page 8: Inputs

    Motion detectors with references ZN1IO-DETEC and ZN1IO-DETEC-N are not compatible with MAXinBOX FC 0-10V VALVE (may report inaccurate measurements if connected to this device). When connected to MAXinBOX FC 0-10V VALVE, the rear micro-switch of model ZN1IODETEC-P should be set to position “Type B”. http://www.zennio.com Technical Support: http://zennioenglish.zendesk.com...
  • Page 9: Individual Binary Outputs

    MAXinBOX FC 0-10V VALVE 2.3 INDIVIDUAL BINARY OUTPUTS MAXinBOX FC 0-10V VALVE incorporates four binary outputs, each of which can be enabled and configured in parameters independently, as long as they are not required by the fan coil control module (see section 2.5) as their typical application in this device is controlling the different fan speeds of the fan coil (up to four).
  • Page 10: Individual 0-10V Analogue Outputs

    MAXinBOX FC 0-10V VALVE 2.4 INDIVIDUAL 0-10V ANALOGUE OUTPUTS MAXinBOX FC 0-10V VALVE incorporates two analogue voltage outputs that provide a signal with a voltage in the range 0 to 10 VDC. This voltage will be in accordance to the percentage values that are received through a specific communication object.
  • Page 11 MAXinBOX FC 0-10V VALVE “[AOx] Output Value (Control)”: this object is provided to receive percentage values from the KNX bus, making the device generate a voltage output between 0 VDC and 10 VDC (proportional to the percentage value). “[AOx] Output Value (Status)”: status object that shows, in terms of percentage, the current value of the analogue output signal.
  • Page 12 MAXinBOX FC 0-10V VALVE  Default: off after an ETS download, and unchanged after a bus power failure.  Custom: this option brings two new parameters: • Initial Status: “Previous”, “On”, “Off”, after either an ETS download or a bus power failure (last will be off on the very first start-up). When selecting “On”, the desired Output Value needs to be configured, in...
  • Page 13: Fan Coil

    MAXinBOX FC 0-10V VALVE 2.5 FAN COIL MAXinBOX FC 0-10V VALVE incorporates one fan coil module that implements all the logic involved in the control of a two-pipe or four-pipe fan coil unit where the fan speed can be switched through relay outputs and the opening and closing of the pipe valves can be commanded through a 0 to 10 VDC signal (depending on the required degree of opening).
  • Page 14 Also within the general configuration of the device, it is necessary to set the valve control type, as either local (the valves will be commanded by MAXinBOX FC 0-10V VALVE itself) or remote (the orders will be sent by MAXinBOX FC 0-10V VALVE bus to a separate valve actuator, through the KNX bus).
  • Page 15 MAXinBOX FC 0-10V VALVE ETS PARAMETERISATION Figure 6 Fan Coil – Configuration. The Configuration screen (see Figure 6) is accessible by default after enabling the Fan Coil function. It contains the following parameters: PIPE CONFIGURATION Type of Fan Coil: “2 pipes” or “4 pipes”. If “2 pipes”, it is necessary to define the available HVAC modes: ...
  • Page 16 MAXinBOX FC 0-10V VALVE FAN CONTROL CONFIGURATION Number of Fan Speeds: up to four fan speeds can be controlled, depending on the fan model. This determines the number of relays required (unneeded relay outputs may be configured as individual binary outputs; see section 2.3).
  • Page 17 MAXinBOX FC 0-10V VALVE the project topology. Ventilation mode can also activate through scenes (please refer to section 2.5.1.4). Alarms: enables or disables the alarm functions (see section 2.5.1.1). Forced Position: enables or disables the forced position function (see section 2.5.1.2).
  • Page 18 This typically translates into a greater opening of the valve (after applying the configured restrictions), which under the local valve control causes a higher-voltage signal in the analogue output of MAXinBOX FC 0-10V VALVE. For valves controlled through other voltage ranges or without a direct proportion...
  • Page 19: Alarms

    Note: alarms always prevail over any other function (i.e., any orders during the alarm state will be ignored). MAXinBOX FC 0-10V VALVE incorporates two independent alarm functions. Alarm 1 has a higher priority over alarm 2. If the fan coil module is under the “alarm 2”...
  • Page 20 MAXinBOX FC 0-10V VALVE ETS PARAMETERISATION After enabling “Alarms” in the Configuration screen (see section 2.5.1), a new tab will be incorporated into the tab tree on the left. Figure 7 Fan Coil – Alarms. While the parameters of alarm no. 1 are shown by default, those of alarm 2 require marking the corresponding checkbox.
  • Page 21 MAXinBOX FC 0-10V VALVE Cyclical Monitoring Period: sets every how much time, at most, the alarm object should be updated from the bus after an initial reception has already taken place. If exceeded, and for safety reasons, the alarm action will be triggered as well.
  • Page 22: Forced Position

    MAXinBOX FC 0-10V VALVE 2.5.1.2 FORCED POSITION It is possible to define a forced position for the Cooling mode and another forced position for the Heating mode. Forced positions consist in a pre-set configuration for the valve opening level and for the fan speed, so that the fan coil unit adopts such configuration when the forced- position trigger object receives the value “1”.
  • Page 23 MAXinBOX FC 0-10V VALVE Moreover, objects “[FCV1] Forced Position: Cooling”, “[FCV1] Forced Position: Heating”, or both (depending on the parameterisation), will be incorporated to the project topology, together with their corresponding status objects. Regarding the parameters: Valve Position: sets, in terms of percentage, the target opening level of the valve.
  • Page 24: Purge

    MAXinBOX FC 0-10V VALVE 2.5.1.3 PURGE The configuration of the valve allows enabling a purge function (one per valve), which consists in opening the selected valve and stopping the fan for a configurable time space. The purge begins when one “1” is received through the corresponding object, and ends when the parameterised time elapses, when one “0”...
  • Page 25 MAXinBOX FC 0-10V VALVE “[FCV1] Valve: Purge Heating Valve”, “[FCV1] Valve: Purge Cooling Valve”. If only one valve is available, they will be replaced by a sole object: “[FCV1] Valve: Purge”. Writing the value “1” to any of these objects triggers the purge of the corresponding valve, while value “0”...
  • Page 26: Scenes

    MAXinBOX FC 0-10V VALVE 2.5.1.4 SCENES It is possible to define up to five scenes so that, when the corresponding value is received from the bus, the module adopts a certain state, which must be defined in terms of the following options: On / Off state of the module.
  • Page 27 MAXinBOX FC 0-10V VALVE Figure 10. Fan Coil - Scenes. Scene “n”: enables or disables scene “n”, which should be then configured through the following additional parameters:  Scene number: sets the value (1-64) that, when received through object “[FCV] Scenes”, will trigger the adoption of the configuration defined next.
  • Page 28: Valves

    (or ICS), i.e., the percentage control variables for heating and for cooling that are received from the thermostat, which itself may be external or any of the thermostats incorporated in MAXinBOX FC 0-10V VALVE. The result of the scaling algorithm and of the application of any other required restrictions makes up the output control signals (or OCS), i.e., the percentage control...
  • Page 29 MAXinBOX FC 0-10V VALVE ETS PARAMETERISATION Figure 12. Fan Coil – Valve(s). http://www.zennio.com Technical Support: http://zennioenglish.zendesk.com...
  • Page 30 MAXinBOX FC 0-10V VALVE The Valve(s) screen (see Figure 12) is accessible by default after enabling the fan coil module. It contains the following parameters: CONTROL SIGNAL SCALING Minimum of the ICS (from Thermostat): sets the minimum value of the input signal, in terms of percentage, that is desired to make the valve open.
  • Page 31 MAXinBOX FC 0-10V VALVE Minimum Time Between Two Successive OCS Orders: sets a minimum time space (from 0 to 3600 seconds or from 0 to 1440 minutes) between consecutive updates of the valve position, either by operating on the valve (local control) or by sending the valve control objects (remote control).
  • Page 32: Minimum Valve Opening

    MAXinBOX FC 0-10V VALVE permits defining a minimum opening level (i.e., a particular position) for each of the valves, so the valves never remain at lower positions, no matter what the OCS value is.
  • Page 33 MAXinBOX FC 0-10V VALVE Figure 13. Fan Coil – Minimum Opening. Minimum Cooling/Heating Mode Opening: sets the minimum opening level (in terms of percentage) required by the valve, to ensure that it never switches to a lower position. Activation mode: sets whether this restriction should apply even when the fan coil module is off (“Even with Fan Coil Off”) or not (“Threshold”).
  • Page 34: Fan

    MAXinBOX FC 0-10V VALVE 2.5.3 FAN The fan speed control of the fan coil module may be manual (the fan speed will be controlled externally; for instance, by the user) or automatic. Under the automatic fan speed control, the fan speed will be controlled by the module itself.
  • Page 35 MAXinBOX FC 0-10V VALVE mode while the valve is open. This ensures that the fan remains in motion whenever the valve stays open. Delays. Please refer to section 2.5.3.1. Silent mode. Please refer to section 2.5.3.2. Custom Start. Please refer to section 2.5.3.3.
  • Page 36 MAXinBOX FC 0-10V VALVE Figure 14. Fan Coil – Fan Configuration. http://www.zennio.com Technical Support: http://zennioenglish.zendesk.com...
  • Page 37 MAXinBOX FC 0-10V VALVE SPEED CONTROL CONFIGURATION Fan Control Mode: sets if the fan speed will be controllable in “Automatic”, “Manual” or “Automatic+Manual” mode. In the latter case, the initial mode after the device start-up is automatic. Moreover, the one-bit object “[FCV1] Fan: Manual/Automatic” will permit switching the mode any time (value “0”...
  • Page 38 MAXinBOX FC 0-10V VALVE ICS and Thresholds 1 to 3 (with Hysteresis) Hysteresis: sets a hysteresis (from 0% to 5%) for the upper thresholds. This helps avoiding continuous speed changes in case the ICS keeps moving around one of the threshold values.
  • Page 39 MAXinBOX FC 0-10V VALVE Figure 15. Non-cyclical fan step control (with three fan speeds). Figure 16. Cyclical fan step control. (with three fan speeds). If desired, the above sequence can incorporate as an additional state the automatic speed mode, so the user can enter this mode through the same fan speed control.
  • Page 40: Delays

    MAXinBOX FC 0-10V VALVE MINIMUM SPEED (MANUAL MODE) Minimum Manual Speed With Open Valve in Cooling Mode: sets a minimum fan speed to ensure the fan never adopts lower speeds while the cooling valve is open and the speed control remains manual. Note that speed 0 is not permitted in any case while the valve is open.
  • Page 41 MAXinBOX FC 0-10V VALVE ETS PARAMETERISATION Figure 17. Fan Coil – Delays. The Delays screen is accessible after enabling the Delays function (see section 2.5.3). It contains the following parameters: Fan Start Delay After Switching to Cooling Mode: sets a delay (from 0 to...
  • Page 42: Silent Mode

    MAXinBOX FC 0-10V VALVE 2.5.3.2 SILENT MODE The Silent Mode function permits restricting the maximum fan speed during the automatic fan speed control. This guarantees that the fan noise level remains low. To that end, one specific binary object is provided to permit entering / leaving the silent mode when desired, as well as the corresponding status object.
  • Page 43: Custom Start

    (i.e., prior to switching to the fan speed determined by the fan coil module or by the user). MAXinBOX FC 0-10V VALVE provides the custom start function to meet such requirement. ETS PARAMETERISATION The Custom Start screen is accessible after enabling such function (see section 2.5.3).
  • Page 44: Logic Functions

    KNX bus, which can be done every time the function is executed, periodically or only when the result differs from the last one. Please refer to the specific “Logic Functions in MAXinBOX FC 0-10V VALVE” user manual (available at the Zennio homepage, www.zennio.com) for detailed information about the functionality and the configuration of the related parameters.
  • Page 45: Thermostats

    MAXinBOX FC 0-10V VALVE 2.7 THERMOSTATS MAXinBOX FC 0-10V VALVE implements two Zennio thermostats which can be independently enabled and fully customised. Please refer to the specific manual “Zennio Thermostat in MAXinBOX FC 0-10V VALVE” (available at the Zennio homepage, www.zennio.com) for detailed information about the functionality and the configuration of the related parameters.
  • Page 46: Manual Control

    MAXinBOX FC 0-10V VALVE 2.8 MANUAL CONTROL MAXinBOX FC 0-10V VALVE allows manually switching the state of its binary and 0- 10V analogue outputs through the respective pushbuttons on the top of the device. A specific pushbutton is therefore available per output.
  • Page 47 MAXinBOX FC 0-10V VALVE The action performed depends on the output type and, in the case of 0-10V analogue outputs, on the press type. For both outputs types, the presses have no effect if the output is disabled in parameters.
  • Page 48 MAXinBOX FC 0-10V VALVE Disabled output: outputs disabled in parameters will not react to button presses under the Test Off mode. Regarding any other secondary functions, the device will behave under the Test Off mode as usual. Button presses during this mode are entirely analogous to the reception of the corresponding orders from the KNX bus.
  • Page 49 MAXinBOX FC 0-10V VALVE ETS PARAMETERISATION The manual control is configured from a specific tab which can be enabled from the General screen (see section 2.1). Figure 20 Manual Control. The only two parameters are: Manual Control: options are “Disabled”, “Only Test Mode Off”, “Only Test Mode On”...
  • Page 50: Annex I: Fan Coil Priorities

    MAXinBOX FC 0-10V VALVE ANNEX I: FAN COIL PRIORITIES The following diagram shows the priority (ordered from higher to lower) of the different functions or orders in MAXinBOX FC 0-10V Valve. Test On Fan Coil Module (Manual Alarm Switch-Off Control)
  • Page 51: Annex Ii: Communication Objects

    MAXinBOX FC 0-10V VALVE ANNEX II: COMMUNICATION OBJECTS “Functional range” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
  • Page 52 MAXinBOX FC 0-10V VALVE 2=Standby 3=Economy 4=Protection C - - W - DPT_Value_Temp -273.00 - 670760.00 [Tx] Setpoint Thermostat Setpoint Input Bytes 16, 46 C - - W - DPT_Value_Temp -273.00 - 670760.00 [Tx] Basic Setpoint Reference Setpoint Bytes 17, 47...
  • Page 53 MAXinBOX FC 0-10V VALVE 83, 112, 141, 1 Byte C T R - - DPT_Scaling 0% - 100% [Ix] Luminosity 0-100% 84, 113, 142, 1 Bit C T R - - DPT_Alarm [Ix] Open Circuit Error 0 = No Error; 1 = Open Circuit Error...
  • Page 54 MAXinBOX FC 0-10V VALVE 162, 167 100, 105, 110, 129, 1 Bit C - - W - DPT_Switch [Ix] [Cy] Channel Lock According to parameters 134, 139, 158, 163, 168 101, 106, 111, 130, 1 Bit C - - W -...
  • Page 55 MAXinBOX FC 0-10V VALVE 0x3 (Dec. by 25%) 0x4 (Dec. by 12%) 0x5 (Dec. by 6%) 0x6 (Dec. by 3%) 0x7 (Dec. by 1%) 0x8 (Stop) 0x9 (Inc. by 100%) 0xA (Inc. by 50%) 0xB (Inc. by 25%) 0xC (Inc. by 12%) 0xD (Inc.
  • Page 56 MAXinBOX FC 0-10V VALVE 1 Bit C T - W - DPT_Switch [Ix] [Long Press] 0/1 Switching Switching 0/1 1 Bit C T - - - DPT_UpDown [Ix] [Long Press] Move Up Shutter Sending of 0 (Up) C T - - -...
  • Page 57 MAXinBOX FC 0-10V VALVE 1 Byte C - - W - DPT_Scaling 0% - 100% [Ix] [Long Press] Dimming Status (Input) 0% - 100% 237, 243, 249, 255 1 Byte C - - W - DPT_Scaling 0% - 100% [Ix] [Long Press] Shutter Status (Input) 0% = Top;...
  • Page 58 MAXinBOX FC 0-10V VALVE 1 Bit C - - W - DPT_Switch [FCVx] Manual Fan: Speed 4 0 = Off; 1 = On 1 Bit C T R - - DPT_State [FCVx] Fan: Speed 0 (Status) 0 = Inactive; 1 = Active...
  • Page 59 MAXinBOX FC 0-10V VALVE 1 Byte C T R - - DPT_Scaling 0% - 100% [FCVx] Cooling Valve (Status) [0…100]% 1 Byte C T R - - DPT_Scaling 0% - 100% [FCVx] Cooling Valve: Control Signal [0…100]% C T R - -...
  • Page 60 Join and send us your inquiries about Zennio devices: http://zennioenglish.zendesk.com Zennio Avance y Tecnología S.L. C/ Río Jarama, 132. Nave P-8.11 45007 Toledo (Spain). Tel. +34 925 232 002. Fax. +34 925 337 310. www.zennio.com info@zennio.com...

Table of Contents