4.8.1 - Optional balancing valves
Two-way valve with waterflow balancing function is
embedded with a differential pressure controller (with or
without pressure test points to control the waterflow
settings). The setting of the valve is shown in Fig. 16.
The manual control knob (16a) is ready fitted to protect
valve stem and pre-set mechanism and facilitates manual
control of valve during commissioning.
Setting procedure:
Remove control knob from the valve (16a)
Loosen knurled nut (16b).
Adjust the desired dial setting with the white knob
(16c) - see table below.
Retighten knurled nut by hand (16d).
Waterflow to adjust [l/h]
1/2' valve
Standard
3/4' valve
1'' valve
ON/OFF
actuator
Standard
Moduling /
3p actua.
Standard
Waterflow range :
200l/h (*) 600l/h (*) 1200l/h (*) 1600l/h (*)
Dial Setting
Min
0.2
0.4
0.5
0.6
0.8
1
1.2
1.4
1.6
1.8
2
2.2
2.4
2.6
2.8
3
3.2
3.4
3.6
3.8
MAX
(*) : Maximum specified water flow on the valve body
WARNING: The valves have to be open when flushing or
pressure testing the system. Strong pressure impacts can
damage closed valves.
Differential pressure across the valve's control path is not
allowed to exceed 400 kPa.
Not
Available
Available Available
Not
Available Available
Not
Available
Available
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
30
100
NA
NA
35
115
200
220
40
130
260
290
50
160
310
250
60
180
380
420
70
210
430
480
80
240
490
550
90
270
550
610
100
300
610
680
110
320
660
740
120
350
730
810
130
380
780
870
140
410
840
940
150
440
900
1000
160
460
960
1070
170
490
1010
1130
180
520
1070
1200
190
550
1130
1260
200
575
1190
1330
4.8.2 - 230 V - Actuators
Two types of valve actuators are provided : electrothermal
actuator (on/off control) or modulating actuator (3-point).
The actuator supply is 230 V a.c.
4.8.3. 24 V - Actuators
Three types of valve actuators are provided : one
electrothermal actuator (on/off control) or two modulating
actuators (3-point or 0-10V).
Both modulating actuators can be operated manually with
a hexagonal key. The 0-10V command voltage range of the
modulating actuator can also be adjusted.
The actuator supply is 24 V a.c.
NOTE: 24V actuators are not compatible with Carrier
controllers (Thermostats A/B/C/D, WTC & NTC).
4.8.4 - Actuator replacement procedure
The actuators on both the chilled water and the hot water
valves may be replaced in case of failure.
WARNING : Do not connect on the same neutral wire the
valve actuator 24 Vac and the controller.
Disconnect the power supply to the unit before carrying
out any work on a unit.
Disconnect the actuator power supply cable.
-
230 V type actuator used with the Carrier numeric
controller: Disconnect the actuator power supply
cable fitted with a quick connector.
-
230 V actuator used with an electronic thermostat:
Remove the plastic protection cover held in place
with two screws. Disconnect the actuator power
supply cable connected to the quick connector.
This can be done by pressing down the spring
tongue using a screwdriver and pulling out the
wire from the appropriate terminal.
Uncouple the faulty actuator. Refitting is by the
reversal of the procedure described above.
WARNING: Ensure that the actuator is firmly screwed to
the valve body (maximum torque 15 N·m).
4.8.5 - Valve body replacement procedure
Disconnect the power supply before carrying out any
work on a unit.
Close the isolating valves on the manifolds.
Unscrew the union nuts to disconnect the flexible
water pipes.
Remove the valve actuators taking care to identify
the cooling and heating valves.
Disconnect the flexible condensate drain pipe which
is held in place by a collar (the collar is not supplied
by Carrier).Remove the two-way or four-way water
flow control valve bodies. Depending how the unit is
configured, the four-way valve coupling may be fitted
with a heating/cooling changeover switch, if so do not
remove it.
Fit the new valve body to the coil (fit new gaskets).
Reconnect the flexible condensate drain pipe which
is held in place by a collar (the collar is not supplied
by Carrier).