10 Wastewater connection

10 Wastewater connection
Tabletop units
Use only steam temperature-resistant pipes
for wastewater drainage. Do not use hoses.
>
Device complies with all relevant regulations
(SVGW, KIWA, WRAS).
>
Connection set for device drain
DN 40/50 Part number: 8720.1031
>
Welding a drain pipe onto the device drain is
not permitted (could result in damage to the
device).
>
Use DN 50 pipe (DN 40 for size 60 units) with
a constant gradient (at least 5% or 3°); do not
reduce pipe diameter.
>
Observe drain dimensioning requirements:
steam generator short-term pump-off rate =
0.7l/s
>
Average wastewater temperature: 65°C
[149°F]
>
Applicable standard: DIN 1986, T1
>
If floor drain has no odor seal, make sure a
2cm [1" ] free outflow zone is in place.
>
We recommend integrating a siphon into the
wastewater connection in order to optimize
energy consumption.
>
Unit sizes 60 through 12 may have both a
wall drain and a floor drain
>
Each device must have its own wastewater
connection (including Combi-Duos).
ATTENTION!