Rational SelfCookingCenter Original Installation Manual page 45

Hide thumbs Also See for SelfCookingCenter:
Table of Contents

Advertisement

8 Gas connection
Notes
Gas connections must only be set up by locally
authorized gas technicians!
Set up the gas connection line in accordance
with the rated thermal load specified on the
type label.
Device malfunction!
If line pressure deviates from connection flow
pressure (>20%), contact gas supply company.
Maintain maximum flow pressure limits:
- 30mbar for natural gas
- 58mbar for LPG
Otherwise:
> do not start the device,
> shut off the gas connection to the device.
Non-functioning device!
Gas components are designed for maximum
connection flow pressure of 65 mbar. Higher
operating pressures are not permitted.
DANGER!
ATTENTION!
ATTENTION!
45

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

CombimasterCombimaster plus

Table of Contents