Figure 19:
Installation Example – Remote-Mounted Blower Pack
A
Steam line must run minimum 12 in (300 mm) vertically before continuing on to the blower pack.
B
All condensate traps must be minimum 12 in (300 mm) below the condensate outlet on the blower pack.
C
The steam line must not exceed the length specified in
hose, or 5× the internal diameter for rigid steam pipes.
D
All condensate traps must have a minimum height of 8 in (200 mm).
E
Steam line must have upslope (minimum 10°) /downslope (minimum 2°), and condensate line must constant minimum downslope of
1 in/48 in (1.2°).
Nortec EL
C
A
D
2582302_C_EN_1611
B
E
Table 6 on page
28. The minimum bend radius is 12 in (300 mm) for a steam
A
Installation
33