Figure 18:
A
Steam line must run minimum 12 in (300 mm) vertically before continuing on to the steam distributor.
B
All condensate traps must be minimum 12 in (300 mm) below the condensate outlet on the steam distributor, and condensate lines
must have a constant minimum downslope of 1 in/48 in (1.2°).
C
The steam line must not exceed the length specified in
hose, or 5× the internal diameter for rigid steam pipes.
D
All condensate traps must have a minimum height of 8 in (200 mm).
E
Steam line must have a minimum of 1 in (25 mm) of pipe insulation over its entire length.
Installation
32
B
D
Installation Example – Rigid Steam Pipe With Insulation
E
C
A
28. The minimum bend radius is 12 in (300 mm) for a steam
Table 6 on page
2582302_C_EN_1611