Nortec EL005 Installation Manual page 35

El series, electrode steam humidifier
Table of Contents

Advertisement

Figure 17:
Installation Example – Steam Distributor Less Than 20 in (500 mm) Above Humidifier
A
Steam line must run minimum 12 in (300 mm) vertically before continuing on to the steam distributor.
B
All condensate traps must be minimum 12 in (300 mm) below the condensate outlet on the steam distributor or the steam line.
C
The steam line must not exceed the length specified in
hose, or 5× the internal diameter for rigid steam pipes.
D
All condensate traps must have a minimum height of 8 in (200 mm).
E
Obstacle
F
Condensate line must connect into a full-size "T" connector installed at the lowest point in the steam line.
Nortec EL
C
D
A
2582302_C_EN_1611
B
C
A
D
F
28. The minimum bend radius is 12 in (300 mm) for a steam
Table 6 on page
E
C
D
B
B
Installation
31