Table 14: Maximum External Fusing, Nortec EL Space 3-Phase
EL Space 005
EL Space 010
EL Space 020
EL Space 030
EL Space 050
EL Space 075
EL Space 100
* Space or RMBP (remote blower pack powered by the humidifier) configuration
5.8.6

Electrical Connections Checklist

Check the following to ensure that the electrical connections for the humidifier have been installed correctly:
… Power supply meet the voltage and current requirements shown on the specification label
on page
9)?
… Power supply have an external dedicated fused disconnect?
… All wiring done according to the wiring diagram and instructions in this manual?
… All cables fastened securely?
… All cables free of tension and pass through cable glands or grommets?
… Electrical installation meet the applicable national and local codes?
… All door panels closed and fastened securely?
Nortec EL
208V/3~
220-240V/3~
7.7
21.5
30
7.7
18.6
25
11.5
31.9
40
11.5
27.6
35
19.0
52.6
70
19.0
45.6
60
28.3
78.6
100
28.3
68.1
90
33.9
94.2
125
37.7
90.6
125
2582302_C_EN_1611
380-415V/3~
440-480V/3~
7.7
10.8
15
7.7
9.3
15
11.5
16.0
20
11.5
13.8
20
19.0
26.4
35
19.0
22.8
30
28.3
39.4
50
28.3
34.1
45
37.7
52.4
70
37.7
45.3
60
550-600V/3~
7.7
7.4
15
11.5
11.0
15
19.0
18.2
25
28.3
27.2
35
37.7
36.2
50