5.8.3
External Connections
The different external connections to the Nortec EL steam humidifier are discussed below.
5.8.3.1 3-Phase Power Supply Connection
Figure 26
shows the 3-phase power supply connections for the Nortec EL steam humidifier.
IMPORTANT! The optional internal fuse is not a substitute for an external fuse. A dedicated
external fused disconnect switch must be installed, and the fuse rating must not exceed the
maximum circuit protection indicated on the specification label – refer to
All wiring must be in accordance with national and local electrical codes.
3
Figure 26:
1
External fused disconnect switch
2
Terminal block, power supply (X0)
3
Optional internal primary fuse
Installation
44
2
3-Phase Power Supply Connections
1
2582302_C_EN_1611
Figure 3 on page
9.
Nortec EL