Figure 16:
A
Steam line must run minimum 12 in (300 mm) vertically before continuing on to the steam distributor.
B
All condensate traps must be minimum 12 in (300 mm) below the condensate outlet on the steam distributor, and condensate lines
must have a constant minimum downslope of 1 in/48 in (1.2°).
C
The steam line must not exceed the length specified in
hose, or 5× the internal diameter for rigid steam pipes.
D
All condensate traps must have a minimum height of 8 in (200 mm).
Installation
30
B
D
Installation Example – Steam Distributor 20 in (500 mm) Above Humidifier
C
A
Table 6 on page
28. The minimum bend radius is 12 in (300 mm) for a steam
2582302_C_EN_1611
Nortec EL