Point Overrides - Trane Tracer SC Operation Manual

System controller
Hide thumbs Also See for Tracer SC:
Table of Contents

Advertisement

Point Overrides

An override refers to the action of a user taking control of a point rather than allowing the system
to control it. Point values can be overridden for output and value points by users who have been
assigned a priority level that gives them override capability. Priority levels of 1–16 exist, with 1
being the highest.The following four priority levels have been pre-assigned for user overrides:
A user with a priority level higher than 13 (a number less than 13), has advanced override capability.
Points appearing with the following icon on their right can be overridden:
Points that have been overridden appear with the following icons:
Overriding a Point
To override a point, click on an override icon, which opens the Override dialog box. Override icons
are located in the far right column of table in which values are listed, or in any status section of a
given piece of equipment, space, or system application.
that appear on an Area status page, both of which can be overridden.
Figure 1.
Point override examples
34
1: Life Safety - Manual
8: Manual Override High
11: Manual Override Medium
13: Manual Override Low (the default for user overrides)
A user override exists:
A temporary user override exists:
Figure
1shows two types of override icons
A user override exists
for this point and can be
overridden.
These points can be
overridden. No
overrides are currently
present.
BAS-SVU025A-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bmsc000aaa011000Bmsc000aaa011100Bmsc000aaa011200