ABB ControlMaster CM10 User Manual page 79

Universal process controllers, 1/8, 1/4 and 1/2 din
Hide thumbs Also See for ControlMaster CM10:
Table of Contents

Advertisement

ControlMaster CM10, CM30 and CM50
Universal process controllers,
Outputs
Controls / retransmission outputs
Number
2 (1 standard, 1 optional)
Type
Configurable as analog or digital pulse
Isolation
Galvanically isolated from the rest of the
circuitry, 500 V for 1 minute
Analog range
0 to 20 mA programmable
Load
750 W Max.
Accuracy
0.2 % of output or ± 10 µVA
Relays
Number
CM10, CM30
4 (1 standard, 3 optional)
CM50
4 (2 standard, 2 optional)
Type
CM10, CM30
Standard with changeover contacts. Optional
contacts selectable as N/O or N/C (by jumper)
CM50
Selectable as N/O or N/C (by jumper)
Contact ratings
CM10
Relay 1
Relays 2, 3, 4
Relays 2, 3, 4
CM30, CM50
5 A, 240 V
Update rate
125 ms
IM/CM/B–EN Rev. H
1
1
1
/
,
/
and
/
DIN
8
4
2
5 A, 240 V
5A, 240 V (max. ambient
40 °C (104 °F)
2A, 240 V (max. ambient
55 °C (131 °F)
Digital input / output
CM10
2 (Optional)
CM30 / CM50
6 (2 standard, 4 optional)
Type
User-programmable as input or output
Minimum input pulse duration – 125 ms
Update rate
125 ms
2-Wire transmitter power supply
CM10
1 (standard)
CM30, CM50
2 (1 standard, 1 optional)
Voltage
24 V DC
Drive
2 loops for each transmitter psu, 45 mA max.
10 Specification
Input
– volt-free or 24 V DC
– 1-signal: 15 to 30 V
– 0-signal: –3 to 5 V
– Conforms to IEC 61131-2
Output
– Open collector output
– 30 V, 100 mA max. switched
– 1-signal: 13.0 to 30.2
– Conforms to IEC 61131-2
77