ControlMaster CM10, CM30 and CM50
Universal process controllers,
...Control / ...Loop 1 Output / ...A/M Select Sources
Manual 1(2)
Config O/P
A/M Toggle
A/M Output
Last Auto O/P
Man – 0%
Man – 100%
Config Value
A/M Config O/P
IM/CM/B–EN Rev. H
1
1
1
/
,
/
and
/
8
4
2
Used when Manual 1(2) Output is set to Config Value.
The source required to toggle between A/M (Auto / Manual)
control modes. When the digital signal is high, the controller is
locked in Manual control mode (the front panel controls [see page
6] and other digital select signals have no effect). When the digital
signal is low Auto control mode is selected. When in the low state,
either the front panel controls or edge-triggered digital signals can
be used to put the controller into Manual control mode.
Sets the (manual) output value to be set when the controller is
put into Manual control mode using A/M Toggle source.
Holds the output at its value prior to switching to Manual
control mode.
Sets the output to 0 %.
Sets the output to 100 %.
Sets the output to the value set in A/M Config O/P.
Used when A/M Output is set to Config Value.
DIN
7 Advanced Level
Auto
Manual
57