ControlMaster CM10, CM30 and CM50
Universal process controllers,
...Device Setup / ...Basic Setup
Loop 1 Split O/P
Instrument Tag
Mains Freq
Config Action
Continue
Hold
Inactive
Reset to Defaults
36
1
1
1
/
,
/
and
/
DIN
8
4
2
These types of outputs split the Control (PID) output signal (see page 32) into 2 signals. The
linear relationship between the PID output and the 2 outputs can be configured in the
control configuration.
A 16-character alphanumeric tag, displayed on Operator pages.
Used to set the internal filters to reduce mains power frequency interference.
The Config Action parameter is used to determine how the controller and controller outputs
behave when the Advanced level is entered – see page 35.
The controller continues to operate as in Operator level. Outputs continue to operate as
normal.
Puts the controller into Manual control mode. When the Configuration level is exited, the
controller returns to the pre-Configuration mode of operation. Digital, relay and analog
outputs are held at their value / state when Configuration mode is entered.
Puts the controller into Manual control mode. When the Advanced level is exited, the
controller returns to the pre-configuration mode of operation.
Digital and relay outputs are turned off. Analog outputs are set to 0 mA.
Resets all configuration parameters to their default values.
7 Advanced Level
IM/CM/B–EN Rev. H