ControlMaster CM10, CM30 and CM50
Universal process controllers,
...Control / ...Loop 1 Output
A/M Select
Sources
Auto Select
Manual 1(2)
Select
Manual 1(2)
Output
Last Auto O/P
Man – 0%
Man – 100%
Config Value
56
1
1
1
/
,
/
and
/
8
4
2
The selection of A/M (Auto / Manual) control modes of operation can be controlled by digital signals;
either from internal digital signals (for example, alarm states) or from external signals via digital inputs
(or digital communications).
The source required to select Auto control mode. Selection is
made on the rising edge of the digital signal.
The source required to select Auto control mode. Selection is
made on rising edge of the digital signal. The output value is
set according to Manual 1(2) Config O/P (see below).
Determines the Manual output value to be set when the
controller is put into Manual control mode (see page 6) using
Manual 1(2) Select source.
Holds the output at its value prior to switching to Manual
control mode.
Sets the output to 0 %.
Sets the output to 100 %.
Sets the output to the value set in Manual 2 Config O/P – see
page 57.
DIN
7 Advanced Level
Auto
Control
Mode
Manual
Control
Mode