ControlMaster CM10, CM30 and CM50
Universal process controllers,
...Basic / ...Loop 1 Control
Mode
Autotune
Autotune is a user-activated feature that enables automatic setting of the controller PID parameters using an 'at setpoint'
type algorithm. Autotune changes the controller output and then monitors the process response to calculate the optimum
PID settings. Autotune uses a relay type function with hysteresis that initiates a controlled oscillation in the process. New
PID parameters are calculated and stored in the controller automatically.
Note. To achieve the best results from Autotune, switch the controller to Manual control mode (see page 6) and adjust the
output until the PV is stable (close to the normal setpoint) before initiating Autotune.
30
1
1
1
/
,
/
and
/
DIN
8
4
2
Turns the Autotune functionality on or off. When set to On, an Autotune can be started from the
Operator level menus – see page 23.
Note. Autotune is enabled only if the control type is PID – see page 32.
6 Basic Level
IM/CM/B–EN Rev. H