ABB ControlMaster CM10 User Manual page 70

Universal process controllers, 1/8, 1/4 and 1/2 din
Hide thumbs Also See for ControlMaster CM10:
Table of Contents

Advertisement

ControlMaster CM10, CM30 and CM50
Universal process controllers,
Number /
Icon
Possible Cause
Message
208.020
Failure of non-volatile memory on communications
NV Error
board or permanent corruption of its data.
Comm Bd
The configuration contains a source that is no longer
Config Error
present or valid.
054.044
Autotune has failed to complete its sequence or has
Tune Lp1 Fail
calculated values outside of its permitted range.
070.040
(066.041)
Autotune has been aborted by the user.
Tuner 1(2) Abort
078.038
(074.039)
Parameters calculated by adaptive control have
Adaptive 1(2)
changed by more than the permitted amounts.
Warn
Table 7.1 Diagnostic Messages (Continued)
68
1
1
1
/
,
/
and
/
DIN
8
4
2
Suggested Action
Acknowledge error. Check communications board is
correctly identified by device.
If problem persists contact local service organization.
Check invalid sources in Diagnostics menu – see section
7.7, page 64.
Check configuration, check I/O required for configuration is
present and correct any illegal use of the invalid signal by
changing configuration or fitting additional option cards.
Check process response. Consider changing the Autotune
dynamic setting – see page 32.
Ensure process is stable and repeat autotune.
If problem persists tune the loop manually.
Check process for issues that may have caused a large
change in its dynamics, for example, a blocked valve.
Reset adaptive control.
Perform a fresh autotune.
7 Advanced Level
IM/CM/B–EN Rev. H

Advertisement

Table of Contents
loading

This manual is also suitable for:

Controlmaster cm30Controlmaster cm50Cm10Cm50Cm30

Table of Contents