Force
Description
Forces a single coil (0X reference) to either
Single Coil
ON or OFF. When broadcast, the function
(05
)
forces the same coil references in all attached
HEX
slaves.
Query
The query message specifies the coil
reference to be forced. Coils are addressed
starting at zero. Coil 1 is addressed as 0.
Force Data = 00 00
Example of a request to set coil 1 (addressed as 0) from slave device 01.
Response
The normal response is an echo of the query,
returned after the coil state has been forced.
MG.10.P2.22 - VLT is a registered Danfoss trademark
(OFF) or FF 00
HEX
HEX
Field Name
Slave Address
Function
Coil Address HI
Coil Address LO
Force Data HI
Force Data LO
Error Check (CRC)
Field Name
Slave Address
Function
Force Data HI
Force Data LO
Quantity of Coils HI
Quantity of Coils LO
Error Check (CRC)
APPENDIX A
(ON).
Example (HEX)
01
05
00
00
FF
00
–
Example (HEX)
01
05
FF
00
00
0A
–
25