Encoder interface, channel 1 htl input without inverse signals, channel 2 htl output
Hide thumbs Also See for Combivert F5:
Table of Contents

Advertisement

Available languages

Available languages

Encoder interface HTL input / HTL output
3.3.2
Output signals channel 2
At the HTL encoder simulation the signal tracks A and B are electrically phase-shifted by
90°. The output signals can be connected optionally as diff erence signal with the respective
inverse tracks or as single-ended signals. The zero signal is output once per revolution with
the same level.
Figure 3.2.2 Output signals HTL
+A
COM
-A
COM
+B
COM
-B
COM
4.
Start-up
After the installation or exchange of an encoder interface some adjustments of the inverter/
servo software have to be done before operation:
• Switch on inverter
• Select application mode
• Select parameter Ec.0 and control whether value „15: inc. input with alarm
24V HTL is entered. The displayed value has to be confi rmed by „ENTER" in
any case.
• Select parameter Ec.10 and control whether value „24: inc.input simulation" is
entered.
• Select parameter Ec.1 and adjust increments per revolution
• Select Ec.42 (Ec.20 upto V2.8) and adjust the encoder breakage recognition
dependent on the case of operation.
5.

Error Messages

Error messages and their meaning are described in Chapter 9 of the application manual.
GB-12
20...26 V
0 V
20...26 V
0 V
20...26 V
0 V
20...26 V
0 V
t