6 Set up
Angled and round plug
connector, cable outlet
18
6 Set up

6.1 Setup procedure

After mounting and electrical connection, VEGABAR 17 is ready for
operation.
VEGABAR 17 delivers a current of 4 ... 20 mA according to the actual
process pressure. Further settings are not necessary.
6.2 Recalibration
Zero and span can be readjusted via potentiometer.
Recommended recalibration cycle: 1 year.
Proceed as follows:
In closed status, unscrew the handle ring and open the instrument
1
Fig. 11: Open the instrument
Adjust zero in unpressurized condition
2
Set a span with a sufficiently precise reference pressure
3
Check zero
4
At least 3-times as exact as the pressure transmitter.