Output 1 - Omega MICROMEGA CN77000 series User Manual

Table of Contents

Advertisement

part
3
O
PERATION

Output 1

Display
Action
oUT
Press MENU
Press ENTER
1
SELF
Press MAX
DSBL
Press ENTER
The output is now under the direct control of the operator and can be adjusted in the run mode, by pressing the MAX and|
Note
MIN buttons. The control value (0 - 99), now displayed in the SV window indicate, approximately in percent, the output. For
example, a setting of 0050 of an analog output of 0~10 Vdc would produce roughly 5 Vdc at the output. Also, to insure
smooth transition when switching to self mode, the proportional control output is left in its last value, when Self Mode is
activated for the first time.
L0
%
%
Press MIN & MAX
0000
Press ENTER
42
: C
M
ONFIGURATION
Response
1) Press MENU, if necessary, until the
2) Display advances to ÒSelfÓ submenu.
SELF SUBMENU
The Self Option allows the output of the controller to be controlled manually from the front panel.
3) Display flashes the current setting of Self, enabled or disabled.
4) Press the MAX button to select between Enable and Disable.
5) If Self enable was selected, Output 1 setting is completed and the display advances to
the next menu.
6) Display advances to the ÒMinimum/Percent LowÓ submenu, if Self is disabled.
MINIMUM/PERCENT LOW SUBMENU
Specify in percent, the minimum value (0000) for control output. If the output is analog, then
the minimum voltage or current, in percent, is specified. If the output is time proportional,
then the minimum duty-cycle, in percent, is specified.
7) Display shows Ò
8) Use MAX & MIN buttons to enter a new value for ÒPercent LowÓ.
9) Press ENTER to store the current setting and to advance to Maximum/Percent High.
ODE
"
out 1
L
% %
0
Ó, and flashes the 10s digit of the current ÒPercent LowÓ setting.
"
prompt appears.