Omega MICROMEGA CN77000 series User Manual page 91

Table of Contents

Advertisement

Command Formats cont.
COMM.PARAMETERS.210 = 000
COMM. PARAMETERS.5 = 0
Example: Set Baud 9600, Odd, 7 Bit, 1 Stop. The command data is 00001101Bin = 0DHex. Send *W100D.
BUSFORMAT.0 = N/A
BUSFORMAT.3 = 0 RS-232
1 RS-485
Example: Set Space, Continuous, RS-232, Echo, Line Feed, N/A. The command data is 00000110Bin = 06Hex. Send *W1F06.
300
BAUD
001
600
010
1200
011
2400
100
4800
101
9600
110 19200
7 Bit Data
1
8 Bit Data
BUS FORMAT.1 = 0 No LF
BUS FORMAT.4 = 0 Continuous
O
: C
PERATION
COMM. PARAMETERS.43 = 00 No Parity
COMM. PARAMETERS.6 = 0
BUS FORMAT.2 = 0 No Echo
1 LF
BUS FORMAT.5 = 0 CR
1 Command
M
ONFIGURATION
ODE
01 Odd
10 Even
11 N/A
1 Stop Bit
1
2 Stop Bit
1 Echo
1 Space
part
3
83