TECHNICAL INFORMATION

Power rating
Protect C.1000
Protect C.2000
Protect C.3000
UPS Input
Rated input voltage
Rectifier voltage range
(without battery
operation, 100 % load,
cos  = 0.8 lag.)
Rectifier voltage range
(without battery operation,
50 % load, cos  = 0.8 lag.)
Nominal frequency
Frequency tolerance
Power consumption at full load (max.)
Protect C.1000
Protect C.2000
Protect C.3000
Bypass voltage range
Mains feedback factor
Connection
UPS Output
Rated output voltage
Nominal frequency
Synchronization range
Synchronization speed
1000 VA (cos φ = 0.8 lag.) 800 W
2000 VA (cos φ = 0.8 lag.) 1600 W
3000 VA (cos φ = 0.8 lag.) 2400 W
1ph~ / N / PE
200 / 208 / 220 / 230 / 240 VAC
176 – 300 VAC
110 – 300 VAC
50 Hz / 60 Hz
(autom. detection or manual)
±10 %
4.8 / 4.6 / 4.4 A
U
= 220 / 230 / 240 VAC
N
8.9 / 8.5 / 8.2 A
U
= 220 / 230 / 240 VAC
N
13.1 / 12.5 / 12.0 A
U
= 220 / 230 / 240 VAC
N
176 VAC – 264 VAC
 ≥0.99 (THDi <5 %)
IEC connector
200 / 208 / 220 / 230 / 240 VAC ±2 %
Power reduction at 200 VAC 20 % /
at 208 VAC 10 %
50 Hz / 60 Hz ±0.2 Hz
(Tolerance in battery mode or free running
in variable-frequency inverter mode)
50 Hz / 60 Hz ±10 %
1 Hz/s
73