Illegal Memory Area; Illegal Step 5 Operations And Statements - Siemens SIMATIC S5-115F User Manual

Simatic s5 programmable controller
Hide thumbs Also See for SIMATIC S5-115F:
Table of Contents

Advertisement

Rules Governing the Use of the S5-115F
Important
!
The following are not permissible
LIR and TNB operations with their source addresses to the I/O area (<1000
>EFFF
) and to the system area (EA0A...EA0E).
H
(LIR and TIR are word operations. The highest accessible address is therefore EFFE
and not EFFF
TIR and TNB operations with destination addresses to the I/O area (<1000
>EFFF
) and to the system area (EA0A...EA0E).
H
(LIR and TIR are word operations. The highest accessible address is therefore EFFE
and not EFFF
L PY and L PW for reading AI modules.

10.7.2 Illegal Memory Area

Direct access to the memory area C400
This memory area is used by the operating system.

10.7.3 Illegal STEP 5 Operations and Statements

In order to guarantee the safety of plants requiring official approval, the possibility of systematic
errors by the user must be eliminated. Systematic errors have the same effect on both subunits.
Note
Organize your programs as clearly as possible!
The following are not permitted
Trick programming
T DL, T DR and T DW operations in DB 1, DB 2, DB 3, configuration DBs and DBs stored on the
EPROM/EEPROM submodule.
DO FW; DO DW, DI and JU R operations in safety-related programs.
Programming of RLO-dependent operations and jump operations within parentheses.
Accessing system data SD5 to SD7.
10-12
).
H
).
H
to EFFF
H
H
with T IR and T NB is illegal.
S5-115F Manual
,
H
H
,
H
H
EWA 4NEB 811 6148-02