Siemens SIMATIC S5-115F User Manual page 328

Simatic s5 programmable controller
Hide thumbs Also See for SIMATIC S5-115F:
Table of Contents

Advertisement

S5-115F Manual
463-4U.AI
CH Rel DQ
4 to 20 mA
with tetrad bits
0 to 20 mA
3
Analog
value
sensor: I
Constellation 4 to 20 mA may only be
configured as channel type 4
Figure 10-29. Type 15 AI, Safety-Related, Non-Intermittent: Two-Channel Sensor with
Current Output; Four-Wire Transducers
Explanation of Figures 10-28 and 10-29
The 470 CH AQ can be connected either to subunit A or B.
Control of the interposing relay DQ is explained in Figure 10-27.
Bold type indicates normal sensor operation.
Permissible modules
Module
463-4U.AI
470-7LA AQ
470-7LB AQ
470-7LC AQ
458-7LA Rel DQ
EWA 4NEB 811 6148-02
Subunit A
-
458 - 7LA
7LA, 0 to 20mA
- 7LC, 4 to 20 mA
470 CH AQ
2
1
0
failsafe
reaction-free
reaction-free
reaction-free
reaction-free
Rules Governing the Use of the S5-115F
AI
As in
subunit A
Analog
value
sensor: I
Characteristics
4 channels, each can be set by jumpers
4 to 20 mA
(load impedance = 62.5 ,
V = 250 to 1250 mV)
0 V
to+10 V
0 mA to +20 mA
8 channels,±10 V or 0 to 20 mA
8 channels, ±10 V
8 channels, 4 to 20 mA
16 * 24 V/0,5 A, not connected to comm. pot.,
relay output
Subunit B
458 - 7LA
CH Rel DQ
with tetrad bits
3
2
1
0
10-45