Siemens SIMATIC S5-115F User Manual page 338

Simatic s5 programmable controller
Hide thumbs Also See for SIMATIC S5-115F:
Table of Contents

Advertisement

S5-115F Manual
Binary weights of the address bits
128 64
ON
16
1
2
32
7
The module is then addressed as follows:
Channel No.
0
1
Address
46.0
46.1
Note
COM 115F CONFIGURE checks the inputs for duplication of addresses, but it does not
check for module address overlap or initial addresses. It can therefore happen that the
address named in the user program does not agree with the address actually accessed.
The user must therefore make sure that the address grid and the initial addresses are
set correctly for all modules.
For this reason, check the settings on the IM 306, AI 463 and CP 523 modules.
EWA 4NEB 811 6148-02
32
16
8
4
2
5
3
2
1
6
4
Figure 10-37. Setting a DIP Switch
2
3
4
5
46.2 46.3
46.4
46.5
46.6
Rules Governing the Use of the S5-115F
The address is equal to the sum of the
weights set by the individual code
switches, e.g.
2+4+8+32=46
6
7
8
9
10
46.7 47.0
47.1
47.2
11
12
13
14
47.3
47.4
47.5
47.6
10-55
15
47.7