Installation Guidelines
Adapter casing
Use an adapter casing to fasten printed circuit boards in double-height Eurocard format to a
mounting rack as you would fasten block-type modules. The adapter casing is required for the
following modules in the S5-115F:
IM 304
IM 314
IM 324
AE 463
CP 523
Figure 3-14. Installing a Printed Circuit Board in an Adapter Casing (6ES5 491-0LB11)
Push the printed circuit board into the casing along the guide tracks. Lock the module into place
with the eccentric locking collars at the top and bottom of the casing.
If an opening remains on the front after the module has been inserted, cover it with a blanking
plate.
Hang the completed unit on the mounting rack and fasten the screws at the top and bottom of
the adapter casing.