I/f start

I/f Start
The
with constant current control. This is useful with high power motors in which the resistance is
low and the tuning of the U/f curve difficult.
Applying the I/f Start function may also prove useful in providing sufficient torque for the motor
at startup.
3
Table 38. Open loop settings
Parameter
Min
0.00
quency
0.0
0.00
age
0
0.0
rent
0
0.0
gain
0.0
tor gain
I/f start
function is typically used with permanent magnet motors (PM) to start the motor
Max
Unit
Default
P3.1.4.2
Hz
Varies
100.0
%
100.0
40.00
%
Varies
1
0
100.0
%
45.0
1
0
100.0
%
100.0
100.0
%
0.0
This menu includes three parameters. See chapter below.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon 100 Application
ID
Description
Provided that the program-
mable U/f curve has been
selected (par. P3.1.4.1) , this
604
parameter defines the mid-
dle point frequency of the
curve.
Provided that the program-
mable U/f curve has been
selected (par. P3.1.4.1), this
605
parameter defines the mid-
dle point voltage of the
curve.
This parameter defines the
zero frequency voltage of
606
the U/f curve. The default
value varies according to
unit size.
Checkbox selection:
B0 = Search shaft frequency
only from same direction as
frequency reference.
1590
B1 = Disable AC scanning
B4 = Use frequency refer-
ence for initial guess
B5 = Disable DC pulses
Defined in percentage of
1610
motor nominal current.
0=Disabled
109
1=Enabled
Scaling factor for motoring
665
side IR-compensation when
torque boost is used.
Scaling factor for generating
667
side IR-compensation when
torque boost is used.