vacon • 155
Selection
number
0
Induction motor (IM)
1
Permanent Magnet Motor (PM)
When this parameter is changed, parameters P3.1.4.2 and P3.1.4.3 will be automatically ini-
tialized according to the selected motor type.
See Table 110 for the initialization values:
Parameter
P3.1.4.2
(Field weakening point
frequency)
P3.1.4.3
(Voltage at field weaken-
ing point)
P3.1.2.4
The automatic motor identification calculates or measures the motor parameters that are
needed for optimum motor and speed control.
Identification Run is a part of tuning the motor and the drive specific parameters. It is a tool for
commissioning and service of the drive with the aim to find as good parameter values as pos-
sible for most drives.
NOTE: Motor nameplate parameters have to be set before executing the identification run.
Selection
number
0
1
2
The automatic identification is activated by setting this parameter to desired value and giving
a start command in the requested direction. The start command to the drive has to be given
within 20 s. If no start command is given within this time the identification run is cancelled, the
parameter will be reset to its default setting and an
The identification run can be stopped at any time with normal stop command and the parame-
ter is reset to its default setting. An
run has failed.
3
Selection name
Induction Motor (IM)
Motor nominal frequency

IDENTIFICATION

Selection name
No action
No identification requested.
Identification at
The drive is run without speed to identify the motor parameters.
standstill
The motor is supplied with current and voltage but with zero fre-
quency. U/f ratio is identified.
Identification with
The drive is run with speed to identify the motor parameters. U/f
motor rotating
ratio and magnetization current are identified.
NOTE:
the motor shaft for accurate results.
Table 109.
Select if an induction motor is used.
Select if a permanent magnet motor is used.
Table 110.
Permanent Magnet Motor (PM)
100,0%
Table 111.
Description
This identification run must be performed with no load on
Identification
Identification
alarm will be launched if the identification
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon 100 Application
Description
Internally calculated
Internally calculated
alarm will be launched.