Checking the shipping packages

The rack rails that are provided for the Symantec Storage Shelf are extensible
to 36" (914mm). This distance is the maximum depth that is allowed between
rack posts. If the distance between rack posts is longer than 36" (914mm) the
rails and the appliance cannot be properly installed. The width of the storage
shelf is 19" (482.6mm).
Ensure that the rack is at least 100 cm (approximately 3 feet) away from the
walls.
Ensure that the clearance between any racks is at least 120 cm (approximately
4 feet) for maintenance, adequate ventilation, and effective heat dissipation.
Ensure that other equipment does not prevent air transfer between the cabinet
and the room. Adequate distance is necessary for cooling of the devices.
Before unpacking devices, check that the packages are intact and undamaged.
Before you unpack the devices, perform the following checks.
To check devices before unpacking
1
Verify that the quantity of the packages which were received matches the
shipping documentation quantity.
2
Check that the packages are intact. If the packages are severely damaged or
are wet, perform Step 4.
3
If the packages are intact, unpack the devices.
4
If the packages are not intact, stop unpacking and identify any problems.
Report the situation to the local engineering manager.
Caution: Store any unpacked systems indoors to protect them from the weather.
If products are damaged, take photographs of the damaged goods and archive
them in a safe place along with any shipping records and invoices.
See ESD-preventive measures" on page 26.