System Architecture - Samsung MIM-B18N Installation Manual

Air conditioner lonworks? gateway
Hide thumbs Also See for MIM-B18N:
Table of Contents

Advertisement

System Architecture

OnOff
controller
RS 485
Outdoor
Unit
Connecting outdoor units and LonWorks Gateway
- You can control up to 80 outdoor units and 128 indoor units using LonWorks Gateway.
*Each communication channel of LonWorks Gateway can be connected with 16 outdoor units.
- The more outdoor units are connected, the longer time takes for tracking.
For the devices which support new communication, set the communication channel
mode on '[System setting]-[Tracking]' menu as 'NEW' and for SIM/PIM which conventional
communication is applied, set the communication channel mode as 'IM'. You cannot
connect indoor & outdoor unit SET which conventional communication is applied to new
communication LonWorks Gateway.
When setting communication channel mode as 'NEW', the address of virtual OnOff control
will be assigned.
Channel 0: Virtual OnOff controller 11, Channel 1: Virtual OnOff controller 12,
Channel 2: Virtual OnOff controller 13, Channel 4: Virtual OnOff controller 14,
Channel 5: Virtual OnOff controller 15
BMS system
Internet
LonWorks Gateway
Max 128 Indoor units
(DVM Series)
BMS Engineering
SAMSUNG Engineering
E-
9