Samsung MIM-B18N Installation Manual page 58

Air conditioner lonworks? gateway
Hide thumbs Also See for MIM-B18N:
Table of Contents

Advertisement

2. DMS system Objects
No.
NV Name
1
nviDigitalOut[6]
2
nviAllOff
3
nvoDigitalOut[6]
4
nvoDigitalIn[8]
5
nvoSystemLock
6
nvoDMSAlarm
7
nvoSystemAlarm
3. Configuration Properties
No.
NV Name
1
nciSndHrtBt
2
nciMinOutTm
3
nciMinDeltaTemp
4
nciDelayStatrup
<Unused Network Variables>
The network variable listed below do exist within our XIF file. However, they are not
explained in this document. They are exclusively intended for internal testing purpose
and should not be used by a user.
◆ nvlVolt
◆ nvoVoltFb
NV Type
SNVT_ switch
Control Digital output of DMS
SNVT_hvac_emerg
Control all indoor unit / ERV OFF
SNVT_ switch
Display Digital output status of DMS
SNVT_ switch
Display Digital input status of DMS
SNVT_switch
Display System Lock status of DMS
Display communication error of the sub
SNVT_ count
device connected to DMS
SNVT_ count
NV Type
SNVT_time_sec
Send Heartbeat
SCPTmaxSendTime
SNVT_time_sec
Minimum Send Time
SCPTminSendTime
SNVT_temp_p
Min. difference before update
SCPTminDeltaTemp
SNVT_time_sec
Delay time after a power-up
SCPTpwrupDelay
Remarks
Remarks