Recommendations
If required, set a value greater than the default update rate (currently, 10s). Any smaller
value does not yield a change in the update pattern.
Associate Values
nvoSpaceTemp, nvoSetPoint
Minimum Temperature Change
This configuration property sets the minimum temperature change required before
the associated output network variable is updated. The associate network variable
will not be updated unless the change is greater than or equal to the Minimum
Temperature Change (nciMinDeltaTemp) configuration value.
Valid Range
The valid range is any value between -273.17ºC and 327.66ºC. Setting
nciMinDeltaTemp = 0.0 (default value) disables the Minimum Temperature Change
mechanism.
Recommendations
If required, set a value greater than 0.1 degree in Celsius. Also, consider the maximum
of the typical operating range which is 50 degree in Celsius.
Associate Values
nvoSpaceTemp, nvoSetPoint
Start-Up Delay
This configuration property controls the minimum period of time that expires before
outputs are retransmitted. It also is the minimum amount of elapsed time after a
power-up or re-establishment of communications before a control action takes
place. This can be used to account for the settle-down time of a network.
All of the output network variable will be updated no faster than the Start-Up Delay
(nciDelayStartup) configuration value. Also, the heartbeat mechanism will not be
enabled unless the elapsed time passes the Start-Up Delay, if used.
Valid Range
The valid range is any value between 0.0 sec and 6,553.4 sec. Setting nciDelayStartup
= 0.0 disables the Start-Up Delay mechanism.
Associate Values
All output network variables
Recommendations
If required, set a value greater than 1 minute which is a settle-down time of the
installed device.