Mains power supply
Make sure that the welding power source is connected to the correct supply voltage
and that it is protected by the correct fuse rating. The standards for the country in
question must be complied with as regards the mains cable area. A protective earth
connection must be made in accordance with regulations.
5.3.1
Recommended fuse sizes and minimum cable areas
Mains voltage
Mains frequency
Fuse (delayed- -action)
85A 35% duty cycle MMA
120A 20% duty cycle MMA
150A 25% duty cycle MMA
Mains cable, area
Welding cable, area MMA
Welding cable, area TIG
*)
NOTE! The mains plug is approved for maximum 16A.
North American version: Mains cable is approved for maximun 18 A.
Australian- version: The mains cable plug is approved for maximum 15A.
Note!
The cable area and fuse rating above comply with Swedish regulations. Use the welding power source
in accordance with the relevant national regulations.
bt26d2e
Tig 150i
230 V ¦10 %, 1--phase
50--60 Hz
10 A
16 A
20 A*)
2
3 x 2.5 mm
2
16 mm
2
16 mm
- - 7 - -
Tig 200i
230 V ¦10 %, 1--fas
50--60 Hz
10 A
16 A
20 A
2
3x2,5 mm
2
16 mm
2
25 mm