Stub Cable Lengths Per Segment - Siemens CPU 313C Hardware And Installation Manual

S7-300 automation system
Hide thumbs Also See for CPU 313C:
Table of Contents

Advertisement

&RQILJXULQJ
/RQJHU FDEOH OHQJWKV
If you want to implement cable lengths above those permitted in a segment, you
must use RS485 repeaters. Information on this topic can be found in the
RS485 repeater product information.
/HQJWK RI WKH VWXE FDEOHV
If bus nodes are connected to a bus segment via stub cables (e.g. PG via a normal
PG cable), then you must consider the maximum possible length of the stub cable.
The following table lists the maximum permitted lengths of stub cables per
segment:
Table 5-26
7UDQVPLVVLRQ UDWH
9.6 kbps to 93.75
kbps
187.5 kbps
500 kbps
1.5 Mbps
3 Mbps to 12 Mbps
1)
At 3 Mbps and higher, use the PG patch cord (Order No. 6ES7 901-4BD00-0XA0) to
connect the PG or PC. You can use multiple PG patch cords of this number in an
installation. Do not use any other type of stub cable.
5-42

Stub cable lengths per segment

0D[ OHQJWK RI VWXE
FDEOHV SHU VHJPHQW
M 96
M 75
M 30
M 10
1)
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
1XPEHU RI QRGHV ZLWK VWXE FDEOH OHQJWK
RI 
 P RU  P
32
32
32
25
20
10
6
3
1)
1)
0 
A5E00105492-03