That is, the DP master writes its Data to these intermediate memory address areas
and the CPU reads these data in the user program, and vice versa.
Figure 9-7 Intermediate memory in a DP CPU operating as a DP slave
$GGUHVV DUHDV LQ LQWHUPHGLDWH PHPRU\
In 67(3 , configure the I/O address areas:
• You can configure up to 32 I/O address areas.
• Maximum length per address area is 32 bytes.
• You can configure a maximum of 244 input bytes and 244 outputs bytes.
The table below shows the principle of address areas. You can also find this figure
in the 67(3 configuration.
Table 9-10
7\SH
1
E
2
A
:
32
Address areas in the
DP master CPU
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03
DP master
Transfer memory
in the address
area
PROFIBUS
Configuration example for the address areas in intermediate memory
0DVWHU
7\SH
DGGUHVV
222
A
0
E
Address areas in the
DP slave CPU
CPU as DP slave
I/Q
6ODYH
/HQJW
DGGUHVV
K
310
2
Byte
13
10
Word
These address area parameters
must be identical for DP master and
DP slave
&RPPLVVLRQLQJ
I/Q
8QLW
&RQVLVWHQF\
Unit
Total length
9-29