Structure Of Station Status 1 (Byte 0) - Siemens CPU 313C Hardware And Installation Manual

S7-300 automation system
Hide thumbs Also See for CPU 313C:
Table of Contents

Advertisement

6WDWLRQ VWDWXV 
Table 11-13 Structure of station status 1 (byte 0)
%LW
0
 DP slave cannot be addressed by DP master.
1
 DP slave is not ready for data exchange.
2
 Configuration data sent by DP master to the DP
slave is inconsistent with slave configuration.
3
 Diagnostic interrupt, generated by a RUN to
STOP transition on the CPU or by the SFB 75
 Diagnostic interrupt, generated by a STOP to
RUN transition on the CPU or by the SFB 75
4
 Function not supported; e.g. changing the DP
address at software level
5
 This bit is always "0".
6
 DP slave type inconsistent with software
configuration.
7
 DP slave was configured by a DP master other
than the master currently accessing the slave.
6WDWLRQ 6WDWXV 
Table 11-14 Structure of station status 2 (byte 1)
%LW
0
 The DP slave requires new parameters and configuration.
1
 A diagnostic message was received. The DP slave cannot resume operation until the error
has been cleared (static diagnostic message).
2
 This bit is always "1" if a DP slave exists with this DP address.
3
 The watchdog monitor is enabled on this DP slave.
4
 DP slave has received control command "FREEZE".
5
 DP slave has received control command "SYNC".
6
 This bit is always "0".
7
 DP slave is disabled, that is, it has been excluded from cyclic processing.
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03
7HVWLQJ )XQFWLRQV 'LDJQRVWLFV DQG )DXOW (OLPLQDWLRQ
'HVFULSWLRQ
Is the correct DP address set on the DP
slave?
Is the bus connector in place?
Does the DP slave have power?
Correct configuration of the RS485
Repeater?
Perform a reset on the DP slave.
Wait for the slave to complete start-up.
Was the software set for the correct
station type or DP slave configuration?
You can read the diagnostic data.
Check configuration data.
-
Was the software set for the right station
type? (parameter assignment error)
The bit is always 1 if, for example, you are
currently accessing the DP slave via PG or
a different DP master.
The configuring master's DP address is
located in the "Master PROFIBUS address"
diagnostics byte.
'HVFULSWLRQ
5HPHG\
11-23