Siemens CPU 313C Hardware And Installation Manual page 194

S7-300 automation system
Hide thumbs Also See for CPU 313C:
Table of Contents

Advertisement

$SSHQGL[
2EVHUYH WKH IROORZLQJ IRU JURXQG FRQQHFWLRQ
• In the same way as with active elements, exercise meticulous care to
interconnect inactive metal elements.
• Always make sure that you have a low-impedance interconnection between
metal elements (e.g. large and highly conductive contact surface).
• The protective insulating finish on varnished or anodized metal elements must
be pierced or removed. Use special contact washers or completely remove the
finish on the point of contact.
• Protect your connecting elements against corrosion (e.g. with a suitable grease)
• Interconnect moving chassis ground elements (e.g. cabinet doors) with flexible
ground straps. Always use short ground straps with a large surface (the surface
is decisive for the diversion of high-frequency currents).
12-8
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents