Shielding Contact Element Underneath Two Signal Modules - Siemens CPU 313C Hardware And Installation Manual

S7-300 automation system
Hide thumbs Also See for CPU 313C:
Table of Contents

Advertisement

The two rows of the shielding contact element allow you install a maximum of
4 shielding terminals.
Figure 7-6 Shielding contact element underneath two signal modules

Bracket of shielding contact element

Edge of bracket where the shielding terminal(s) must be placed.
Shielding terminals

7HUPLQDWLQJ FDEOHV
Only one or two shielded cables can be terminated per shielding terminal (see the
figure below). The cable is clamped in at the stripped cable shielding.
1. Strip the cable shielding to a length of at least 20 mm.
2. Clamp in the stripped cable shielding underneath the shielding contact clamp.
Push the shielding clamp towards the module (1) and feed the cable through
underneath the clamp (2).
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03
P S
C P U
3
7KH GLDJUDP LOOXVWUDWHV XQGHU QXPEHU
:LULQJ
1
1
2 2
7-15