Siemens CPU 313C Hardware And Installation Manual page 202

S7-300 automation system
Hide thumbs Also See for CPU 313C:
Table of Contents

Advertisement

$SSHQGL[
&DEOHV IRU 
DC voltage (> 60 V and
≤ 400 V), unshielded
AC voltage (> 25 V and
≤ 400 V), unshielded
DC and AC voltage (> 400 V),
unshielded
ETHERNET
12-16
DQG FDEOHV IRU 
Bus signals, shielded
(PROFIBUS)
Data signals, shielded
(programming devices,
operator panels, printers,
counter inputs, etc.)
Analog signals, shielded
DC voltage (≤ 60 V),
unshielded
Process signals (≤ 25 V),
shielded
AC voltage (≤ 25 V),
unshielded
Monitors (coaxial cable)
DC voltage (> 60 V and
≤ 400 V), unshielded
AC voltage (> 25 V and
≤ 400 V), unshielded
DC and AC voltage (> 400 V),
unshielded
Bus signals, shielded
(PROFIBUS)
Data signals, shielded
(programming devices,
operator panels, printers,
counter inputs, etc.)
Analog signals, shielded
DC voltage (≤ 60 V),
unshielded
Process signals (≤ 25 V),
shielded
AC voltage (≤ 25 V),
unshielded
Monitors (coaxial cable)
DC and AC voltage (> 400 V),
unshielded
ETHERNET
Others
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
5XQ 
In separate bundles or cable
ducts (no minimum clearance
necessary)
In common bundles or cable
ducts
LQVLGH FDELQHWV
In separate bundles or cable
ducts (no minimum clearance
necessary)
RXWVLGH FDELQHWV
On separate cable racks with a
clearance of at least 10 cm
LQVLGH FDELQHWV
In separate bundles or cable
ducts (no minimum clearance
necessary)
RXWVLGH FDELQHWV
On separate cable racks with a
clearance of at least 10 cm
In common bundles or cable
ducts
In common bundles or cable
ducts
In separate bundles or cable
ducts with a clearance of at least
50 cm
A5E00105492-03