Configuring

5.8.6 Overview: Grounding

CPU 31xC
The figure below shows you the complete assembly of an S7-300 with CPU 31xC
with a power supply from TN-S mains.
Apart from powering the CPU, the PS 307 also supplies the load current for the
24 VDC modules.
Note: The arrangement displayed does not correspond with the physical
arrangement; it was merely selected to give you a clear overview.
L1
L2
L3
N
PE
1
Figure 5-11 Grounding concept for the S7-300 with CPU 31xC
Table 5-10
(1)
Main switch
(2)
Short-circuit/overload protection
(3)
Load power supply (galvanic isolation)
(4)
This connection is automatically generated for the CPU 31xC
5-26
Rail
L1
N
3
AC
AC
AC
DC
AC
DC
Connection of the load voltage reference potential
The diagram illustrates under number
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
Low-voltage distribution
e. g. TN-S system (3 x 400 V)
Cabinet
CPU
PS
4
1
µP
L +
M
Signal modules
Ground bus in cabinet
2
AC 24 to 230 V load circuit for
AC modules
2
DC 5 to 60 V load circuit for
non-isolated DC modules
2
DC 5 to 60 V load circuit for
isolated DC modules
SM