Group HANDLING TOTALIZER
Function description HANDLING TOTALIZER
RESET ALL TOTALIZERS
Use this function to reset the totals (including all overflows) of the totalizers (1 to 2) to
"zero" (= RESET).
Options:
NO
YES
Factory setting:
NO
!
If the transmitter has a status input and if it is appropriately configured, a reset for the
totalizer (1 to 2) can also be triggered by a pulse (see the ASSIGN STATUS INPUT func-
tion, Page 48).
FAILSAFE MODE
Use this function to define the response of all totalizers (1 to 2) to a fault.
Options:
STOP
The totalizer is paused until the fault is rectified. The totalizer stops at the last value prior
to the occurrence of the error.
ACTUAL VALUE
The totalizer continues to count based on the current flow measured value. The fault is
ignored.
HOLD VALUE
The totalizer continues to count the flow based on the last valid flow value (before the
fault occurred).
Factory setting:
STOP