Group Handling Totalizer - Endress+Hauser Proline t-mass 65F Manual

Thermal mass flow measuring system
Hide thumbs Also See for Proline t-mass 65F:
Table of Contents

Advertisement

Device Functions Proline t-mass 65
Endress+Hauser
9

Group HANDLING TOTALIZER

Function description HANDLING TOTALIZER
RESET ALL TOTALIZERS
Use this function to reset the totals (including all overflows) of the totalizers (1 to 2) to
"zero" (= RESET).
Options:
NO
YES
Factory setting:
NO
!
If the transmitter has a status input and if it is appropriately configured, a reset for the
totalizer (1 to 2) can also be triggered by a pulse (see the ASSIGN STATUS INPUT func-
tion, Page 48).
FAILSAFE MODE
Use this function to define the response of all totalizers (1 to 2) to a fault.
Options:
STOP
The totalizer is paused until the fault is rectified. The totalizer stops at the last value prior
to the occurrence of the error.
ACTUAL VALUE
The totalizer continues to count based on the current flow measured value. The fault is
ignored.
HOLD VALUE
The totalizer continues to count the flow based on the last valid flow value (before the
fault occurred).
Factory setting:
STOP
Note!
9 Group HANDLING TOTALIZER
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Proline t-mass 65i

Table of Contents