Group Totalizer - Endress+Hauser Proline t-mass 65 PROFIBUS DP Manual

Thermal mass flow measuring system
Hide thumbs Also See for Proline t-mass 65 PROFIBUS DP:
Table of Contents

Advertisement

7 Group TOTALIZER

20
7
Group TOTALIZER
SELECT TOTALIZER
SUM
OVERFLOW
CHANNEL
Device Functions Proline t-mass 65 PROFIBUS DP
Function description TOTALIZER
Use this function to select the totalizer.
Options:
TOTALIZER 1
TOTALIZER 2
Factory setting:
TOTALIZER 1
!
Note!
If the PROFILE-GSD option is selected in the SELECTION GSD function, only the
TOTALIZER 1 option is available in this function.
!
Note!
This function is available separately for each totalizer. The selection of the current
totalizer takes place in the SELECT TOTALIZER function (see above).
Use this function to display the current totalizer value incl. unit.
Display:
max. 7-digit floating-point number, including unit (e.g. 15467.04 kg)
!
Note!
This function is available separately for each totalizer. The selection of the current
totalizer takes place in the SELECT TOTALIZER function (see above).
Use this function to display totalizer overflow aggregated since measuring began.
Total flow quantity is represented by a floating-point number consisting of max.
7 digits. You can use this function to view higher numerical values (>9,999,999) as
overflows.
The effective quantity is thus the total of the OVERFLOW function plus the value
returned by the SUM function.
Example:
Reading for 2 overflows: 2 E7 kg (= 20,000,000)
The value returned by the SUM function = 196,845.7 kg
Effective total quantity = 20,196,845.7 kg
Display:
Integer with exponent, including unit, e.g. 2 E7 kg
!
Note!
This function is available separately for each totalizer. The selection of the current
totalizer takes place in the SELECT TOTALIZER function (see above).
Use this function to assign the measured variable to the totalizer.
Options:
OFF
MASS FLOW
CORRECTED VOLUME FLOW
Factory setting: (TOTALIZER 1 and 2)
MASS FLOW
!
Note!
The totalizer is reset to 0 as soon as the selection is changed.
Endress+Hauser

Advertisement

Table of Contents
loading

Table of Contents