Prepare the electrical connections

4.1
Cable selection
Use shielded twisted pair wiring (18-12 AWG).
For the RS-485 bus, use shielded twisted pair wiring, preferably with an
impedance of 120  (typically 24 AWG).
4.2
Cable gland/conduit
For explosion-proof/ flameproof installations, only use cable glands or conduit
entry devices certified explosion-proof or flameproof.
4.3
Power supply (Vdc)
Approval type
None
Non-sparking/Energy limited
Intrinsically safe
FISCO
Explosion-proof/Flameproof
4.4
4-20 mA/HART communication
Figure 1. Wiring Diagram
A.
Field Communicator
B.
Approved IS barrier
(for Intrinsically Safe installations only)
C.
HART modem
Note
Rosemount 5400 Level Transmitters with Flameproof/Explosion-proof output have a
built-in barrier; no external barrier needed.
HART
F
OUNDATION
16 - 42.4
9 - 32
16 - 42.4
9 - 32
16 - 30
9 - 30
N/A
9 - 17.5
20 - 42.4
16 - 32
Quick Start Guide
Fieldbus
RS-485 with Modbus
8-30 (max. rating)
N/A
N/A
N/A
8-30 (max. rating)
A
C
1
2
3
4
5
6
7
8
9
0
D
B
D.
Current meter
Load resistance (≥250 
E.
F.
Power supply
F
E
11