Quick Start Guide
Step 2: Configure device
HART Device Revision 2
1. Select Configure/Setup > Basic Setup.
2. Configure steps 1-5 in the Basic Setup.
(Variable Mapping, Geometry, Environment, Volume, and Analog Out)
3. Select Finish.
4. Run Measure and Learn.
5. Select Restart Device.
HART Device Revision 3
1. Select Configure > Guided Setup.
2. Select Level Measurement Setup and follow the instructions.
3. Run Verify Level to check your level measurement.
4. Consider optional setup, such as Volume and Display.
F
OUNDATION
1. Select Configure > Guided Setup.
2. Select Level Measurement Setup and follow the instructions.
3. Optional: Select Volume Calculation Setup.
4. Run Measure and Learn.
5. Select Restart Measurement.
Table 2. F
Function
Tank Type
Tank Bottom Type
Tank Height
Still-pipe/Bridle Measurement
(enable function)
Pipe Inner Diameter
Process Condition
Product Dielectric Constant
Volume Calculation Method
Diameter
Length
Volume Offset
7.0

Safety Instrumented Systems (4-20 mA only)

For Safety Certified installations, refer to the Rosemount 5400
Manual.
20
Fieldbus
Fieldbus Parameters
OUNDATION
F
Fieldbus parameters
OUNDATION
TRANSDUCER_1100>GEOM_TANK_TYPE
TRANSDUCER_1100>GEOM_TANK_BOTTOM_TYPE
TRANSDUCER_1100>GEOM_TANK_HEIGHT
TRANSDUCER_1100>SIGNAL_PROC_CONFIG
TRANSDUCER_1100>ANTENNA_PIPE_DIAM
TRANSDUCER_1100>ENV_ENVIRONMENT
TRANSDUCER_1100>ENV_DIELECTR_CONST
TRANSDUCER_1300>VOLUME_CALC_METHOD
TRANSDUCER_1300>VOL_IDEAL_DIAMETER
TRANSDUCER_1300>VOL_IDEAL_LENGTH
TRANSDUCER_1300>VOL_VOLUME_OFFSET
June 2017
Reference