Advertisement

Shut-off valve
The shut-off valve is in the main leaving water temperature zone,
and is connected to the heating/cooling output.
NOTICE
The output of the shut‑off valve is NOT configurable. Do
NOT change the value of setting [F‑0B]. Only connect NO
(normal open) shut‑off valves.
Operation range
Depending on the average outdoor temperature, the operation of the
unit in space heating or space cooling is prohibited.
Space heating OFF temp: When the averaged outdoor temperature
rises above this value, space heating is turned OFF to avoid
overheating.
#
Code
[A.3.3.1]
[4-02]
14°C~35°C (default: 19°C)
The same setting is also used in
automatic heating/cooling changeover.
Space cooling On temp: ONLY applicable for EWYQ006+008BAVP.
When the averaged outdoor temperature drops below this value,
space cooling is turned OFF.
#
Code
[A.3.3.2]
[F-01]
10°C~35°C (default: 20°C)
The same setting is also used in
automatic heating/cooling changeover.
Automatic heating/cooling changeover
ONLY applicable for EWYQ006+008BAVP. The end-user sets the
desired operation mode on the user interface: Heating, Cooling or
Automatic (see also operation manual/user reference guide). When
Automatic is selected, the changing of the operation mode is based
on:
▪ Monthly allowance for heating and/or cooling: the end-user
indicates on a monthly base which operation is allowed ([7.5]: both
heating/cooling or heating ONLY or cooling ONLY). If the allowed
operation mode changes to cooling ONLY, the operation mode
changes to cooling. If the allowed operation mode changes to
heating ONLY, the operation mode changes to heating.
▪ Averaged outdoor temperature: the operation mode will be
changed in order to ALWAYS be within range determined by the
space heating OFF temperature for heating and the space cooling
On temperature for cooling. If the outdoor temperature drops, the
operation mode switches to heating and vice versa. Note that the
outdoor
temperature
will
"8 Configuration" on
page 46).
When the outdoor temperature is between the space cooling On and
the space heating OFF temperature, the operation mode remains
unchanged unless the system is configured in room thermostat
control with one leaving water temperature zone and quick heat
emitters. In that case, the operation mode will change based on:
▪ Measured indoor temperature: besides the heating and the
cooling desired room temperature, the installer sets a hysteresis
value (e.g. when in heating, this value is related to the desired
cooling temperature) and an offset value (e.g. when in heating,
this value is related to the desired heating temperature). Example:
the desired room temperature in heating is 22°C and in cooling
24°C, with a hysteresis value of 1°C and an offset of 4°C.
Changeover from heating to cooling will occur when the room
temperature rises above the maximum of the desired cooling
temperature added by the hysteresis value (thus 25°C) and the
desired heating temperature added by the offset value (thus
26°C). Oppositely, changeover from cooling to heating will occur
when the room temperature drops below the minimum of the
EWAQ+EWYQ006+008BAVP + EK(2)CB07CAV3 +
EKMBUHCA3V3+9W1
Packaged air-cooled water chillers and packaged air to water heat
pumps
4P492901-1 – 2017.06
Description
Description
be
time-averaged
(see
desired heating temperature subtracted by the hysteresis value
(thus 21°C) and the desired cooling temperature subtracted by the
offset value (thus 20°C).
▪ Guard timer to prevent too frequent changing from heating to
cooling and vice versa.
Changeover settings related to the outdoor temperature (ONLY
when automatic is selected):
#
Code
[A.3.3.1]
[4-02]
Space heating OFF temp. If the outdoor
temperature rises above this value, the
operation mode will change to cooling:
14°C~35°C (default: 19°C)
[A.3.3.2]
[F-01]
Space cooling On temp. If the outdoor
temperature drops below this value, the
operation mode will change to heating:
10°C~35°C (default: 20°C)
Changeover settings related to the indoor temperature. ONLY
applicable when Automatic is selected and the system is configured
in room thermostat control with 1 leaving water temperature zone
and quick heat emitters.
N/A
[4-0B]
Hysteresis: Ensures that changeover is
ONLY done when necessary. Example:
The space operation mode ONLY
changes from cooling to heating when
the room temperature drops below the
desired heating temperature subtracted
by the hysteresis.
1°C~10°C, step: 0.5°C (default: 1°C)
N/A
[4-0D]
Offset: Ensures that the active desired
room temperature can be reached.
Example: if heating to cooling
changeover would occur below the
desired room temperature in heating, this
desired room temperature could never
be reached.
1°C~10°C, step: 0.5°C (default: 3°C)
8.3.2

Heat source settings

Backup heater
Backup heater operation mode: defines when backup heater
operation is enabled or disabled. This setting is only overruled when
backup heating is required during defrost operation or malfunctioning
of the outdoor unit (when [A.6.C] is enabled).
#
Code
[A.5.1.1]
[4‑00]
Backup heater operation:
▪ 0: Disabled
▪ 1 (default): Enabled
[A.5.1.3]
[4‑07]
Defines whether backup heater second
step is:
▪ 1: Allowed
▪ 0: NOT allowed
In this way it is possible to limit the
backup heater capacity.
N/A
[5-00]
Is backup heater operation allowed
above equilibrium temperature during
space heating operation?
▪ 1: NOT allowed
▪ 0: Allowed
8 Configuration
Description
Description
Installer reference guide
57